Câble de commande résistant au feu (2 - 4 noyaux) 300 - 500V paramètre
Conductor | rated voltage 300/500v | ||||||
Without Earth Conductor | With Earth Conductor | ||||||
No. of Core X Cross Section | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx. Weight | Nominal Overall Diameter | Approx. Weight |
No*mm² | No./mm | mm | mm | mm | kg/km | mm | kg/km |
2 Cores | |||||||
2x1.5 | 7/0.53 | 0.5 | 0.5 | 7.7 | 70 | 8.2 | 80 |
2x2.5 | 7/0.67 | 0.5 | 0.5 | 8.8 | 100 | 9.6 | 120 |
2x4 | 7/0.85 | 0.5 | 0.5 | 9.8 | 140 | 10.5 | 170 |
3 Cores | |||||||
3x1.5 | 7/0.53 | 0.5 | 0.5 | 8.7 | 90 | 10.5 | 100 |
3x2.5 | 7/0.67 | 0.5 | 0.5 | 9.5 | 125 | 10.7 | 150 |
3x4 | 7/0.85 | 0.5 | 0.5 | 11.5 | 180 | 12.5 | 220 |
4 Cores | |||||||
4x1.5 | 7/0.53 | 0.5 | 0.5 | 10.3 | 105 | 12.2 | 120 |
4x2.5 | 7/0.67 | 0.5 | 0.5 | 11 | 155 | 13 | 190 |
4x4 | 7/0.85 | 0.5 | 0.5 | 12.5 | 255 | 13.5 | 270 |
Description du câble de commande résistant au feu 300 - 500V (2 - 4 noyaux)
Tension nominale: 300 / 500V
norme de base: BS 7211
conducteur: fil de cuivre recuit nu, fil multiple conforme à la Norme CEI (en) 60228;Classe 2
réfractaire: ruban de verre Mica
matériau isolant: PVC (xlpe)
gaine: composé lszh selon BS 7655 - 6.1;
plage de température de fonctionnement (état fixe): - 30°Classe C– + 90°C
plage de température de fonctionnement (état de déplacement): - 20°Classe C– + 50°C
rayon de flexion minimal: 6 fois le diamètre extérieur
résistance à l'isolation:20 mΩ X km (20)°
température du court - circuit:250.°Code Postal:
Circuit Integrity | IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); |
CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); | |
NF C32-070-2.3(CR1) | |
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; |
VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); | |
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* | |
Reduced Fire Propagation (Vertically-mounted bundled wires | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30- |
004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 | |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; |
CEI 20-37/2-1 ; BS 6425-1* | |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; |
CEI 20-37/2-2 ; BS 6425-2* | |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; |
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* | |
No Toxic gases | NES 02-713; NF C 20-454 |
Application d'un câble de commande résistant au feu 300 - 500V (2 - 4 noyaux)
Les câbles sont conçus pour être utilisés dans des installations essentielles au maintien et à l'entretien de l'intégrité des circuits dans le système d'alimentation électrique.Les câbles
sont largement utilisés dans les tunnels souterrains, l'éclairage de secours, les systèmes d'alarme incendie, les circuits de commande et d'alimentation électrique, les centrales électriques, les ascenseurs, les escaliers mécaniques et les grands bâtiments.