Paramètres du câble Cu / PVC h07v - r
AWG | No. of Cores x Nominal Cross-Sectional Area | Nominal Thickness of Insulation | Nominal Overall Diameter | Nominal Copper Weight | Nominal Weight |
# x mm² | mm | mm | kg/km | kg/km | |
H07V-R | |||||
16(7/24) | 1 x 1.5 | 0.7 | 3 | 14.4 | 23 |
14(7/22) | 1 x 2.5 | 0.8 | 3.6 | 24 | 35 |
12(7/20) | 1 x 4 | 0.8 | 4.2 | 39 | 51 |
10(7/18) | 1 x 6 | 0.8 | 4.7 | 58 | 71 |
8(7/16) | 1 x 10 | 1 | 6.1 | 96 | 120 |
6(7/14) | 1 x 16 | 1 | 7.2 | 154 | 170 |
4(7/12) | 1 x 25 | 1.2 | 8.4 | 240 | 260 |
2(7/10) | 1 x 35 | 1.2 | 9.5 | 336 | 350 |
1(19/13) | 1 x 50 | 1.4 | 11.3 | 480 | 480 |
2/0(19/11) | 1 x 70 | 1,4 | 12.6 | 672 | 680 |
3/0(19/10) | 1 x 95 | 1,6 | 14.7 | 912 | 930 |
4/0(37/12) | 1 x 120 | 1,6 | 16.2 | 1152 | 1160 |
300MCM(37/11) | 1 x 150 | 1,8 | 18.1 | 1440 | 1430 |
350MCM(37/10) | 1 x 185 | 2,0 | 20.2 | 1776 | 1780 |
500MCM(61/11) | 1 x 240 | 2,2 | 22.9 | 2304 | 2360 |
1 x 300 | 2.4 | 24.5 | 2940 | ||
1 x 400 | 2.6 | 27.5 | 3740 |
Cu / PVC h07v - R Description
Conducteurs: torons de cuivre recuits classe 2
Tension nominale: 450 / 750v
isolation: PVC
rayon de flexion: 15 fois le diamètre total
norme: BS en50525 - 2 - 31, CEI 60227.As / NZS 5000.1
température du court - circuit: + 160 °C
ignifugeant: iec60332 - 1
résistance à l'isolation: 10 mΩ x km
Application de composites Cu / PVC - h07v - r
H07v - U pour la pose de protection à l'intérieur de l'équipement ou de l'équipementlightings.it Dans des conditions sèches, elles sont généralement installées sous les tuyaux et dans les tuyaux installés sur les surfaces plâtrées intérieures.Il s'agit d'un bon choix d'installations de production, d'équipement de câblage interne, de commutateurs et de panneaux de distribution ou d'un fil multibrin plus épais qui est nécessaire.